b.)
Place the jumper into the test ports* marked T and H on I34M-1
for 20 seconds and then remove jumper.
During
this portion of the procedure the compressor and condensing fan
should
stop operating when jumper is installed.
Also
the large white gear on the face of the I34M-1 should slowly rotate
clockwise. If the above has occurred the unit will remain in
the ejection cycle
for up to 5 minutes then it will dump the ice (if water was
present and frozen) and also send water into the mold in preparation
for the next
cycle.
This
will indicate that the I34T is in need of replacement.
Proceed
to the next section on replacing the I34T. If not then recheck
the I34M-1 (see
instructions) and wiring harness (see
instructions).
*Verify
that the complete amount of exposed wire is seated fully into
the test port. |