Page 2 - Raritan Momentary Control Owners Manual L483-v0216
P. 2
WIRING NOTES: for Wiring o 2 Wire - AWG to mm CONVERSIONS 8 16.0 25.0 35.0
Distances are from source to unit and back to source.
2
1.
Distance from power source to remote intake pump MUST be
AWG
12
10
16
14
4
6
2
2.
included when determining total distance.Same wire size MUST be
used for lower base and remote intake pump.
6.0
10.0
2.5
4.0
1.5
mm
2
Recommended conductor wire minimum AWG (mm ) for 3% volt-
3.
Feet to Meters
age drop.
Recommended conductor sizes are based on 105 C rated insulation.
50
15
25
Feet
40
20
10
30
4.
Refer to ABYC Standards for other insulation ratings.
5.
For 120/240 VAC units use 12VDC specifications from transformer
to unit. Meter 3.1 4.6 6.1 7.6 9.2 12.2 15.2
Sea Water Model - Recommended Wire and Fuse/Circuit Breaker Size
Circuit Remote Pump
Units Breaker/fuse Discharge Only 15 20 30 40 50
Voltage Amp. draw feet feet feet feet feet
size (amps) Amp. draw
Atlantes 12 VDC 30 18 10
Marine Elegance 10 AWG 8 AWG 6 AWG 6 AWG 4 AWG
SeaEra 25 13 10
Atlantes 20 10 5
Marine Elegance 24 VDC 14 AWG 14 AWG 12 AWG 10 AWG 10 AWG
SeaEra 15 7.5 5
Pressurized Freshwater Model - Recommended Wire and Fuse/Circuit Breaker Size
Circuit 10 15 20 30 40 50
Units Amp. feet feet feet feet feet feet
Voltage Breaker/fuse draw
size (amps)
Atlantes 25 18
Marine Elegance 12 VDC 12 AWG 10 AWG 10 AWG 8 AWG 6 AWG 6 AWG
SeaEra 25 13
Atlantes 15 10
Marine Elegance 24 VDC 14 AWG 12 AWG 10 AWG 10 AWG 8 AWG 6 AWG
SeaEra 15 7.5
Mounting controls: Fig.1
A. Mounting control box:
1. Locate a place for control box near toilet. Do not install
box more than six feet away to avoid excessive voltage
drop
2. Route wires between toilet and control
B. Switch Panel:
1. Cut out a hole per Fig. 1, mark
mounting holes using wall plate as guide.
2. Route wire to the toilet and control.
3. Secure control using sealant with two
screws.
C. Sea/fresh control:
1. Follow Switch Panel instructions above.
2 L483 0216jlc